CN EN
  • SHHP-240/15k3
  • SHHP-240/15k3

Using SiC technology, through modular design and core control algorithms, convert AC to DC, suitable for electrolyzers, meeting the technical requirements of hydrogen production power supply for reliability, efficiency, and harmonics.

Product Introduction Product Features Technical Parameter

Using SiC technology, through modular design and core control algorithms, convert AC to DC, suitable for electrolyzers, meeting the technical requirements of hydrogen production power supply for reliability, efficiency, and harmonics.

Intelligent:Battery management, insulation monitoring, online expansion, intelligent sleep function; High system efficiency(≥ 95%), safe hydrogen production.
Modular:High power density, space saving;Convenient and efficient maintenance;Parallel design, easy to expand
Advantages:Low harmonic (<3%), better power quality;High power factor(≥0.99);High /Low voltage ride through,HVRT/LVRT.
Reliability:Strong adaptability to the power grid;Strong environmental adaptability, operating at -20℃ and an altitude of 1000 meters.
Product AC/DC+DC/DC two-stage topology hydrogen production power supply
AC Parameters Input Voltage 305Vac-478Vac
Input frequency 45Hz-65Hz
Power Factor >0.99(fully loaded)
THD ≤± 3% (10% -100% load rate)
Connection mode 3P-5Wires,Top inlet
DC Parameters Output current 600A
Output voltage range 140Vdc-200Vdc
Output ripple ≤0.5%(0MHz~20MHz P-P voltage)
Voltage regulation ≤±0.6%
Output power 180kW(Modular expandable)
Output power accuracy ≤1%
Current sharing ≤±3%
System Parameter Dynamic response The overshoot shall not exceed ± 5% of the output voltage setting value, and the recovery time shall not exceed 200 μ s
Efficiency ≥95%
Dimension W600mm×D1200mm×H2500mm
Noise ≤60dB
Safety Insulation monitoring function
Environment Cooling mode Fan-cooling
Working temperature -20℃-55℃(working range); -5℃-40℃(No derating working range)
Altitude ≤1000m(1000m+, derating output)
Related humidity ≤90%(40±2℃)
Protection level IP20(Adjust according to user needs)
Lightning Protection AC SPD Capable of withstanding voltage pulses (10/700us, 5kV) and (8/20us, Impact of In=20kA
DC SPD Capable of withstanding voltage pulses (10/700us, 5kV) and (8/20us, Impact of In=10kA
Reliability MTBF Power system reliability ≥ 2 × 105h, rectifier module reliability ≥ 4 × 105h
Seismic resistance Meet the seismic requirements of YD 5083-2005 and YD 5096-2005, and pass the seismic test with an intensity of 8